Voltage Drop in Consumer Installations According to BS 7671

 



Voltage drop in a consumer’s installation can be a contentious issue. However, it is an important aspect of installation design since if it is too high some certain equipment will not function correctly or will not function at all.


Rules Applied: 

  • 525.1 In the absence of any other consideration, under normal service conditions the voltage at the terminals of any fixed current-using equipment shall be greater than the lower limit corresponding in the product standard relevant to the equipment.
  • 525.100 Where fixed current-using equipment is not the subject of a product standard the voltage at the terminals shall be such as not to impair the safe functioning of that equipment.
  • 525.101 The above requirements are deemed to be satisfied if the voltage drop between the origin of the installation (usually the supply terminals) and a socket-outlet or the terminals of fixed current-using equipment, does not exceed that stated in Appendix 4 Section 6.4

Calculating Voltage Drop 


When calculating voltage drop due consideration should be given to the following: 
  • motor starting currents; in-rush currents
  • control voltages (particularly those associated with computerized systems).

Notes: 
  1. Motor control contactors and relays can ‘drop out’ if the coil voltages fall towards 80% of the operating voltage.
  2. The effects of harmonic currents may also need to be considered and included in the calculation.
  3. Voltage transients and voltage variations due to an abnormal operation can be ignored.


The maximum voltage drop values can be taken from the table shown below:

For 230 Volts Network

Allowable Voltage Drop Based on BS 7671

*The voltage drop within each final circuit on Private Networks, should not exceed the values given in (i) above for Public Networks

For 400 Volts Network

Allowable Voltage Drop Based on BS 7671

*The voltage drop within each final circuit on Private Networks, should not exceed the values given in (i) above for Public Networks


When calculating the voltage drop in a circuit, the design current can be taken as being either the equipment rated current or, where there are a number of loads, the total connected load multiplied by a diversity factor. 

Note: If the total circuit length exceeds 100 meters, the limits given in Table 4Ab may be increased by 0.005% per meter up to a maximum of 0.5%.

The voltage drop can be apportioned throughout the system circuits as the designer wishes, but the final circuit voltage drop is limited to the values given for Public Networks, regardless of whether it is a Public Network or a Private Network.

In case that the supply voltage at the origin is lower than the nominal 230/400V, the designer needs to consider the effect of the minimum permissible supply voltage. This is a maximum of 6% below the nominal supply voltage, which equates to 216.2V (for 230 V network ) and 376V (for 400 V network) respectively.

Reference: 

Electrical Contractors Association Fact Sheet | Download

3 comments:

  1. You've written an excellent post, and you've shared it with us. Your article provided me with some unique and useful knowledge Experienced Domestic Electrician in Sittingbourne. I appreciate you sharing this text with us.

    ReplyDelete
  2. When your website or blog goes live for the first time, it is exciting. That is until you realize no one but you and your. 2cl2fm

    ReplyDelete
  3. Really, this is impressive article which you have shared here. It is provides me an interesting knowledge. I request you to keep sharing such blogs for testing and tagging perth. Keep it up.

    ReplyDelete

Select Topics

electric protection Electrical Design power system protection Electrical Safety Fault Analysis Electrical Machines protective relaying circuit breaker electrical protection Electrical Equipment Technical Topics Electrical Installation Power System BS7671 short circuit analysis DC Circuit Earthing System Transformer power system analysis what Direct Current System Energy Efficiency Generator IEC standard Manual Resources Transmission Lines Unbalanced Fault Analysis electrical motor electrical testing grid automation power system automation smart grid tutorial video ebook how motor control substation automation symmetrical components AC Machines Advance Circuit Theory IEC 60364 Renewable Energy Voltage Drop Calculation current transformer electrical grounding schneider electric Circuit Analysis fuse generator protection power system stability quiz switchboard transformer protection ABB Manuals AC Circuit Busbar DC Machines GE Whitepapers General Electric Line to Line Fault National Electrical Code arc flash earth fault loop impedance electric vehicle electrical wiring power plant power system operation selective coordination switchgear video tutorial 3D printing ABB AREVA AUS/NZ 3000 Assignment help Busway Current Nomenclatures Electricity Spot Market G3 technology IEEE C37.2 IEEE/ANSI Device Numbers MiCom NFPA 70E Philippine Electrical Code Terms of use Theoretical UFES VFD ampacity battery building wiring capacitor circuit breaker curve cooling system cooper bussman disruptive technologies electrical earthing electrical harmonics energy industry energy savings engineering education iec 61850 inspection checklist learning process bus protective bonding single line to ground fault transmission line protection variable frequency drive voltage compensation voltage transformer voltage unbalance