How to Calculate Motor Circuit Branch Circuit Protection According to NEC 430.52

 



Motor Circuit Protection

Motor circuit protection describes the short-circuit protection of conductors supplying power to the motor, the motor controller, and motor control circuits/conductors. 430.52 provides the maximum sizes or settings for overcurrent devices protecting the motor branch circuit. A branch circuit is defined in Article 100 as “The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).”


NEC Motor Control Protection Requirements

Note that the branch circuit extends from the last branch circuit overcurrent device to the load. Table 430.52 lists the maximum sizes for Non-Time-Delay Fuses, Dual Element (Time-Delay) Fuses, Instantaneous Trip Circuit Breakers, and Inverse Time Circuit Breakers. Sizing is based on full load amp values shown in Table 430.247 through 430.250, not motor nameplate values. For example, the maximum time-delay fuse for a 10HP, 460 volt, 3 phase motor with a nameplate FLA of 13 amps would be based on 175% of 14 amps, not 175% of 13 amp.


Courtesy: Cooper Bussmann

 



Standard sizes for fuses and fixed trip circuit breakers, per 240.6, are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000 5000, and 6000 amps. Additional standard fuse sizes are 1, 3, 6, 10, and 601 amps. 

The exceptions in 430.52 allow the user to increase the size of the overcurrent device if the motor is not able to start. All Class CC fuses can be increased to 400%, along with non-time-delay fuses not exceeding 600 amps. Time-delay (dual-element) fuses can be increased to 225%. All Class L fuses can be increased to 300%. Inverse time (thermal-magnetic) circuit breakers can be increased to 400% (100 amp and less) or 300% (larger than 100 amps). Instant trip circuit breakers may be adjusted to 1300% for other than Design B motors and 1700% for energy efficient Design B motors. 
  • 430.52(C)(2) reminds the user that the maximum device ratings which are shown in a manufacturer’s overload relay table must not be exceeded even if higher values are allowed by other parts of 430.52. 
  • 430.52(C)(3) details the requirements that instant-trip CBs can only be used if part of a listed combination motor controller. 

Courtesy: Cooper Bussmann

No comments:

Select Topics

electric protection Electrical Design power system protection Electrical Safety Fault Analysis Electrical Machines protective relaying circuit breaker electrical protection Electrical Equipment Technical Topics Electrical Installation Power System BS7671 short circuit analysis DC Circuit Earthing System Transformer power system analysis what Direct Current System Energy Efficiency Generator IEC standard Manual Resources Transmission Lines Unbalanced Fault Analysis electrical motor electrical testing grid automation power system automation smart grid tutorial video ebook how motor control substation automation symmetrical components AC Machines Advance Circuit Theory IEC 60364 Renewable Energy Voltage Drop Calculation current transformer electrical grounding schneider electric Circuit Analysis fuse generator protection power system stability quiz switchboard transformer protection ABB Manuals AC Circuit Busbar DC Machines GE Whitepapers General Electric Line to Line Fault National Electrical Code arc flash earth fault loop impedance electric vehicle electrical wiring power plant power system operation selective coordination switchgear video tutorial 3D printing ABB AREVA AUS/NZ 3000 Assignment help Busway Current Nomenclatures Electricity Spot Market G3 technology IEEE C37.2 IEEE/ANSI Device Numbers MiCom NFPA 70E Philippine Electrical Code Terms of use Theoretical UFES VFD ampacity battery building wiring capacitor circuit breaker curve cooling system cooper bussman disruptive technologies electrical earthing electrical harmonics energy industry energy savings engineering education iec 61850 inspection checklist learning process bus protective bonding single line to ground fault transmission line protection variable frequency drive voltage compensation voltage transformer voltage unbalance