Motor's contribution is the current generated by a motor or motors during a short circuit condition. It represents a small but important value that is needed to determine the maximum short circuit current available and thereby establishing the short circuit rating of electrical equipment. Regardless of the size or voltage rating of a motor, it can be demonstrated that motor contribution is present during a fault. 


During a short circuit condition, the system voltage will decay. A stable voltage supply no longer exists. The rotating magnetic field in the rotor will attempt to support the reduced voltage condition by becoming a power source. The motor is now providing additional current into the faulted electrical system. This phenomenon is called "motor contribution". 

 

The amount of current is dependent on the motor impedance. At first, there is an asymmetrical current containing both AC and DC components. Lack of a stable voltage supply causes the AC component to decay when the rotor flux begins to drop. Without a stable voltage supply, the transient DC component also decays. 


Related Article: In What Situation that an Induction Motor Can Accidentally Become a Generator?


The current supplied by the motor at first differ in frequency from the system frequency due to motor slip. The motor and load inertia determine the rate of decay. It is understood that the difference does not have an effect on the short circuit calculation.


The motor impedance Zm determines the AC components value. The motor impedance is made up of a resistive Rm component and reactive component Xm. The resistive component is always much less in value than the reactive component; therefore, for calculating motor contribution the inductive component Xm will provide a conservative value. 


The electrical system's X/R ratio determines the rate of decay of the DC component. When X equals zero, there is only asymmetrical current with no DC component. With R equals to zero, the DC component would never decay. One can say there will always be both resistance and reactive components in the system. Induction motor contribution typically lasts from one to four cycles from time equal to zero during a short circuit condition. However, synchronous motors' short circuit contribution can last from six to eight cycles. 


Electric Motor | Source: Tekwell Services


The main difference is the induction motor does not have an excitation capability of a synchronous motor; therefore, it cannot maintain voltage for the same amount of time. In either case, the motor contribution is present during the first cycle. ANSI standard C37.010 offers guidance when calculating motor contribution for a group of low voltage motors if detail motor data are not available. Assuming a motor contribution of four times rated full load current is acceptable. 


The standard arrived at this value by assuming the motor contribution of 3.6 times rated current came from 75% induction motors and 4.8 times rated current from 25% synchronous motors.


It has become an accepted practice to use four times rated full load current in the absence of detailed data on synchronous motors and induction motors of unknown size on the system. Multipliers of 3.6, 4 and 4.8 times are less than the motor lock rotor current. This could account for a reduction of motor contribution at the start of the short circuit; and this assumption seems to explain this reduction. Approximations are a useful tool in the absence of detail motor data. 


Related Article: How to Develop Sequence Network in an Unbalanced Faulted System?


For large motors or groups of large motors, lock rotor current, typically 5 to 7 times full load current is used in place of the motor actual impedance will provide a very conservative value. For small motors or groups of small motors it is recommended that a value of 0.20 to 0.28 per unit be used in place of actual motor impedance data. 


In the very early stages of a project, the amount of detailed motor data or even a complete motor list is not available. Using approximation or a "rule of thumb" is acceptable. At this point, the engineer needs to determine orders of magnitude of short circuit current. Is the system short circuit value approaching, or has it exceed a short circuit level. The engineer knows that the assumptions have provided a conservative value. 


The important point is the engineer has a motor contribution factored into his calculation and his assumptions have provided a conservative value. After gathering all the equipment data the engineer may then conduct a detailed short circuit study before purchasing equipment.


Reference: 

Title: Understanding Short Circuit Motor Contribution

Author: Darrell G Broussard, P.E. Sr. Specification Engineer GE Industrial Solutions

Publisher: General Electric

Document: PDF | Download

1 comment:

  1. Your blog had very good knowledge and that gave huge instructions and that was really commendable ideas. you have provided good knowledge on this topic please share more information with us.local electrician near me

    ReplyDelete

Select Topics

electric protection Electrical Design power system protection Electrical Safety Fault Analysis Electrical Machines protective relaying circuit breaker electrical protection Electrical Equipment Technical Topics Electrical Installation Power System BS7671 short circuit analysis DC Circuit Earthing System Transformer power system analysis what Direct Current System Energy Efficiency Generator IEC standard Manual Resources Transmission Lines Unbalanced Fault Analysis electrical motor electrical testing grid automation power system automation smart grid tutorial video ebook how motor control substation automation symmetrical components AC Machines Advance Circuit Theory IEC 60364 Renewable Energy Voltage Drop Calculation current transformer electrical grounding schneider electric Circuit Analysis fuse generator protection power system stability quiz switchboard transformer protection ABB Manuals AC Circuit Busbar DC Machines GE Whitepapers General Electric Line to Line Fault National Electrical Code arc flash earth fault loop impedance electric vehicle electrical wiring power plant power system operation selective coordination switchgear video tutorial 3D printing ABB AREVA AUS/NZ 3000 Assignment help Busway Current Nomenclatures Electricity Spot Market G3 technology IEEE C37.2 IEEE/ANSI Device Numbers MiCom NFPA 70E Philippine Electrical Code Terms of use Theoretical UFES VFD ampacity battery building wiring capacitor circuit breaker curve cooling system cooper bussman disruptive technologies electrical earthing electrical harmonics energy industry energy savings engineering education iec 61850 inspection checklist learning process bus protective bonding single line to ground fault transmission line protection variable frequency drive voltage compensation voltage transformer voltage unbalance