Instrument Transformers in Power System Protection
Electrical Substation | Source: General Electric |
Protection or measuring devices require data on the electrical rating of the equipment to be protected. To obtain this data, following intermediary devices are needed:
- voltage transformers (VT)
- current transformer (CT)
These devices fulfill the following functions:
- reduction of the value to be measured (e.g.1500/5 A)
- galvanic isolation
- providing the power required for data processing and for protection operation itself.
Current Transformers
The CTs are characterized by the following
values.
CT voltage
This is the operating voltage applied to the
CT primary. Note that the primary is at the
HV potential level and that one of the
secondary terminals is generally earthed.
As for other equipment, the following is also
defined :
maximum1 min. withstand voltage at
standard frequency
maximum impulse withstand voltage.
e.g. for 24 kV rated voltage, the CT must
withstand 50 kV voltage for 1 min at 50 Hz
and 125 kV impulse voltage.
Related Article: Types and Classes of Current Transformer Used in Protective Relaying
Rated transformation ratio
It is usually given as the transformation ratio
between primary and secondary current
I1/I2. Secondary current is generally 5 A
or 1 A.
Current Transformer | Source: Nicore Magnetic Cores |
Accuracy level
It is defined by the composite error for the
accuracy limit current.
e.g. 5P10 means 5% error for 10 In
10P15 means 10% error for 15 In
5P and 10P are the standard accuracies
classes.
5 In, 10 In, 15 In, 20 In are the standard
accuracy limit currents.
The accuracy limit factor
is the ratio
between the accuracy limit current and the
rated current.
Class X is another way of specifying CT
characteristics based on "knee-point
voltage" (fig.1, CT response in the saturated
state).
Accuracy level power
Secondary power at rated current for which
the accuracy level is guaranteed. Expressed
in VA, it indicates the power that the
secondary can deliver for its rated current,
while respecting the rated accuracy class.
It represents the total consumption of the
secondary circuit, i.e. the power consumed
by all the connected devices as well as the
connecting wires.
If a CT is loaded at a power rating lower
than its accuracy level power, it's actual
accuracy level is higher than the rated
accuracy level. Likewise, a CT that is loaded
too much loses accuracy.
Admissible short time current
Expressed in RMS kA, the maximum current
admissible for 1 second (Ith) (the secondary
being short-circuited) represents CT thermal
overcurrent withstand. The CT must have
the capacity to withstand short-circuit current
for the time required to clear it. If the clearing
time t is other than 1 sec., the current the CT
can withstand is Ith / Vt.
Electrodynamic withstand expressed in peak
kA is at least equal to 2.5 x Ith.
Normal values of rated currents
At the primary (in A)
10 - 12.5 - 15 - 20 - 25 - 30 - 40 -
50 - 60 - 75 and multiples or decimal
submultiples.
When subjected to very strong current, the
CT becomes saturated, i.e. the secondary
current is no longer proportional to the
primary current.
The current error which corresponds to the
magnetization current becomes very high.
CT Saturation Point or Knee Point |
Knee Point Voltage - This is the point on the current transformer magnetization curve at which a 10% increase in voltage V requires a 50% increase in magnetization current Im.
For direct time overcurrent protection, if
twice the setting current does cause
saturation, the operation is ensured no matter
how strong the fault.
For IDMT overcurrent protections, saturation
must not be reached for current values in
the working part of the operation curve (a
maximum of 20 times the setting current).
However, there are special types of CT that do not saturate. This are specific "wide band" current sensors. These sensors, most often without magnetic circuits and therefore not subject to saturation. Linked to an electronic device, their response is linear. These CTs are used and supplied with the digital technology protection units. They only require knowledge of the primary rated current.
Voltage Transformers
Voltage transformers reduced the high voltage across the power system into a value that can be connected to small protective relays. Normally, the secondary side of the VT used for protective relaying has a maximum voltage of 120 Volts.
Voltage Transformers | Source: Indiamart |
The voltage transformer have the following
characteristics (IEC186).
- Electrical system frequency generally 50 or 60Hz,
- system's highest primary voltage (secondary voltage is standardized 100, 100/ , 110, 110/ Volts),
- rated voltage factor
- VA power rating and accuracy class
Note: 3-transformer assembly (requires 1 insulated high voltage terminal per transformer)
A few additional key concepts for understanding voltage transformers:
- Polarity - refers to the relative directions of the instantaneous voltages on the primary and secondary windings and is determined by the arrangement of the windings and the transformer connection terminals. Polarity is an instrument transformer is always subtractive, meaning that its primary terminals H1 and H2 and its secondary terminals X1 and X2 are arranged so that the voltage measured between a primary terminal and its adjacent secondary terminal will be the difference between the two voltages. Instrument transformer polarity is usually indicated with dot marks or plus/minus marks on the transformer and on drawings. Polarity is not important for simple voltage and current measurements, but it is crucial for power measurements and certain protective relay elements such as differential and directional.
- Burden - is simply the term for the load on an instrument transformer’s secondary winding. The burden consists of the relays or meters that are connected to the instrument transformer’s secondary winding. It also includes the impedance of the conductors between the secondary winding and the load. Voltage transformers are available with standard burden ratings that are designated with letter codes, as defined in IEEE standard C57.13. VTs usually have a maximum power rating of less than 500 Volt Amperes.
- Accuracy - there are two sources of error in instrument transformers: ratio error and phase error. Instrument transformers must be designed to ensure that even with these errors, secondary voltages and currents accurately represent primary voltages and currents. IEEE C57.13 establishes voltage transformer accuracy classes of 0.15, 0.3, 0.6, and 1.2, which applies when the VT secondary voltage is between 90% and 110% of rated voltage. Burden and accuracy are closely related to voltage transformers.
Reference:
- Protection Guide and Control
- Publisher: Merlin Gerin | Download
ReplyDeleteYou can look up to the Call Girls as the perfect travel companion.Low budget Call Girls in Surat There are people who like to travel a lot and do not feel like doing so because of the lack of a quality companion. Our Low Rate Call Girls in Surat can go on to fill the void in this regard.Bengali Call Girls in Gurgaon When you travel without anyone it can be boring affair and when you rely on the services of these Air hostess Call Girls in Faridabad, there is a commitment on your part to bring back the lost charm in your life.Air hostess Call Girls in Faridabad Be it a short or a long trip,Call Girls whatsapp number in Jaipur they are more than happy to accompany you.
Genuinely good post about your experience. Your post is interesting to read. I like your writing method, Please share more about Ferrite Cores for sale online in USA Good luck with next upcoming update.
ReplyDelete