Types and Classes of Current Transformer Used in Protective Relaying

Current Transformer in the Substation | Source


The importance of current transformers in the transmission and distribution of electrical energy cannot be over-emphasized. The efficiency of current transformers, and associated voltage transformers, affect the accurate metering and effective protection of the transmission and distribution circuits and connected plants.


Generally, there are three different types of CTs:

  • High remanence type CT 
  • Low remanence type CT 
  • Non remanence type CT 


The behavior of CTs according to different standards but belonging to the same type is in principle the same. 


High remanence CTs 

The high remanence type has no given limit for the remanent flux. The CT has a magnetic core without any air gaps and the remanent flux might remain for almost infinite time. The remanent flux can be up to 70-80% of the saturation flux. Typical examples of high remanent type CTs are class P, PX, TPS, TPX according to IEC 60044 and non-gapped class C according to ANSI/IEEE. 3.2 


Low remanence CTs

The low remanence type has a specified limit for the remanent flux. The magnetic core is provided with small air gaps to reduce the remanent flux to a level that does not exceed 10% of the saturation flux. Examples are class TPY according to IEC 60044-6 and class PR according to IEC 60044-1. 3.3 


Non remanence CTs

The non remanence type CT has practically negligible level of remanent flux. The magnetic core has relatively large air gaps in order to reduce the secondary time constant of the CT (to lower the needed transient factor) which also reduces the remanent flux to practically zero level. An example is class TPZ according to IEC 60044-6. 


Read: What are the Conditions in Selecting Current Transformer in Protective Relaying


Current Transformer Standards


The behaviour of inductive CTs in accordance with IEC 60044-1 and IEEE C57.13 is specified for steady state symmetrical AC currents. The more recent standard IEC 60044-6 is the only standard that specifies the performance of inductive CTs (classes TPX, TPY and TPZ) for currents containing exponentially decaying DC components of defined time constant. This section summarises the various classes of CTs.


IEC 60044-1


Class P 

Class P current transformers are typically used for general applications, such as overcurrent protection, where a secondary accuracy limit greatly in excess of the value to cause relay operation serves no useful purpose. Therefore a rated accuracy limit of 5 will usually be adequate. 


"When relays, such as instantaneous ‘high set’ overcurrent relays, are set to operate at high values of overcurrent, say 5 to 15 times the rated current of the transformer, the accuracy limit factor must be at least as high as the value of the setting current used in order to ensure fast relay operation."


Rated output burdens higher than 15VA and rated accuracy limit factors higher than 10 are not recommended for general purposes. It is possible, however, to combine a higher rated accuracy limit factor with a lower rated output and vice versa. When the product of these two exceeds 150, the resulting current transformer may be uneconomical and/or of unduly large dimensions. 


Characteristics of Class P CTs


Class PR

A current transformer with less than 10% remanence factor due to small air gaps for which, in some cases, a value of the secondary loop time constant and/or a limiting value of the winding resistance may also be specified.


Class PX 

A current transformer of low leakage reactance for which knowledge of the transformer secondary excitation characteristic, secondary winding resistance, secondary burden resistance and turns ratio is sufficient to assess its performance in relation to the protective relay system with which it is to be used. 


Class PX is the definition in IEC 60044-1 for the quasi-transient current transformers formerly covered by class X of BS 3938, commonly used with unit protection schemes. 


Class PX type CTs are used for high impedance circulating current protection and are also suitable for most other protection schemes. 


IEC 60044-6


Class TPS

Protection current transformers specified in terms of complying with class TPS are generally applied to unit systems where balancing of outputs from each end of the protected plant is vital. This balance, or stability during through fault conditions, is essentially of a transient nature and thus the extent of the unsaturated (or linear) zones is of paramount importance. 


"It is normal to derive, from heavy current test results, a formula stating the lowest permissible value of Vk if stable operation is to be guaranteed".  


The performance of class TPS current transformers of the low (secondary) reactance type is defined by IEC 60044-6 for transient performance. In short, they shall be specified in terms of each of the following characteristics: 

  • Rated primary current 
  •  Turns ratio (the error in turns ratio shall not exceed ±0.25%) 
  •  Secondary limiting voltage 
  •  Resistance of secondary winding
Class TPS CTs are typically applied for high impedance circulating current protection. 

Class TPX 

The basic characteristics for class TPX current transformers are generally similar to those of class TPS current transformers except for the different error limits prescribed and possible influencing effects which may necessitate a physically larger construction. 

Class TPX CTs have no air gaps in the core and therefore a high remanence factor (70-80% remanent flux). The accuracy limit is defined by the peak instantaneous error during the specified transient duty cycle. 

Class TPX CTs are typically used for line protection.

Class TPY

Class TPY CTs have a specified limit for the remanent flux. The magnetic core is provided with small air gaps to reduce the remanent flux to a level that does not exceed 10% of the saturation flux. They have a higher error in current measurement than TPX during unsaturated operation and the accuracy limit is defined by peak instantaneous error during the specified transient duty cycle. 

Class TPY CTs are typically used for line protection with auto-reclose. 

 Class TPZ

For class TPZ CTs the remanent flux is practically negligible due to large air gaps in the core. These air gaps also minimise the influence of the DC component from the primary fault current, but reduce the measuring accuracy in the unsaturated (linear) region of operation. 


The accuracy limit is defined by peak instantaneous alternating current component error during single energization with maximum DC offset at specified secondary loop time constant. 

Class TPZ CTs are typically used for special applications such as differential protection of large generators.


EEE C57.13


Class C

The CT design is identical to IEC class 10P but the rating is specified differently. Refer to Appendix B for equivalent ratings and conversion formulae between IEC and IEEE classifications. 


Reference:

  • Burdens & Current Transformer Requirements of MiCOM Relays | Download
  • Publisher: AREVA

1 comment:

  1. Any offset current coursing through a high impedance gadget will make an undesirable voltage show up across the gadget, adding to the voltage estimation.عالية الجهد مكثف السيراميك

    ReplyDelete