Electric Motor Protection in Case of Voltage Unbalance and Single Phasing

 

Voltage Unbalance


When the voltage between all three phases is not equal, the current values in each phase will also become unbalanced. According to NEMA, the maximum voltage unbalance is limited only to 1% both for electric motors and generators. When the voltage unbalance occurs, the current increases gradually in the motor winding which if it continues, the motor will be damaged. Therefore it is necessary derate the motor according to the expected voltage unbalance. 



If in case, the derating is not possible and the voltage unbalance still persists, the loading in this case must be reduced accordingly. This method must be considered to avoid the damage of the equipment.


Causes of Unbalanced Voltage 

  • Connecting unequal single-phase loads. This is why many consulting engineers specify that loading of panelboards be balanced to ± 10% between all three phases.
  • Open delta connections. 
  • Transformer connections open - causing a single-phase condition. 
  • Improper tap settings on transformer banks.  
  • Transformer impedances (Z) of single-phase transformers connected into a “bank” not the same. 
  • The capacitors used in power factor correction capacitors are not the same or some of them are off the line

Insulation Life The effect of voltage unbalance on the insulation life of a typical T-frame motor having Class B insulation, running in a 40°C ambient, loaded to 100%, is as follows:




Note that motors with a service factor of 1.0 do not have as much heat withstand capability as do motors having a service factor of 1.15. Older, larger U-frame motors, because of their ability to dissipate heat, could withstand overload conditions for longer periods of time than the newer, smaller T-frame motors.

Insulation Classes 


The following shows the maximum operating temperatures for different classes of insulation. 
  • Class A Insulation = 105°C 
  • Class B Insulation = 130°C 
  • Class F Insulation = 155°C 
  • Class H Insulation = 180°C

Reference: 
  • Cooper Bussman

No comments:

Select Topics

electric protection Electrical Design power system protection Electrical Safety Fault Analysis Electrical Machines protective relaying circuit breaker electrical protection Electrical Equipment Technical Topics Electrical Installation Power System BS7671 short circuit analysis DC Circuit Earthing System Transformer power system analysis what Direct Current System Energy Efficiency Generator IEC standard Manual Resources Transmission Lines Unbalanced Fault Analysis electrical motor electrical testing grid automation power system automation smart grid tutorial video ebook how motor control substation automation symmetrical components AC Machines Advance Circuit Theory IEC 60364 Renewable Energy Voltage Drop Calculation current transformer electrical grounding schneider electric Circuit Analysis fuse generator protection power system stability quiz switchboard transformer protection ABB Manuals AC Circuit Busbar DC Machines GE Whitepapers General Electric Line to Line Fault National Electrical Code arc flash earth fault loop impedance electric vehicle electrical wiring power plant power system operation selective coordination switchgear video tutorial 3D printing ABB AREVA AUS/NZ 3000 Assignment help Busway Current Nomenclatures Electricity Spot Market G3 technology IEEE C37.2 IEEE/ANSI Device Numbers MiCom NFPA 70E Philippine Electrical Code Terms of use Theoretical UFES VFD ampacity battery building wiring capacitor circuit breaker curve cooling system cooper bussman disruptive technologies electrical earthing electrical harmonics energy industry energy savings engineering education iec 61850 inspection checklist learning process bus protective bonding single line to ground fault transmission line protection variable frequency drive voltage compensation voltage transformer voltage unbalance